What size wire for 30 amps at 12V?

30 A over 10 ft one way at 12 V with a 3% drop limit needs 6 AWG copper. By current rating alone 10 AWG would do (35 A), so longer runs are decided by voltage drop and need thicker wire. The table gives every length from 5 to 50 ft.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 6 AWG (13.3 mm²) copper or larger.

Voltage drop sets the size. 8 AWG would drop 3.14%, over your 3% limit. Ampacity alone would allow 10 AWG.

Check: 6 AWG (13.3 mm²)

Load current30 A
Wire in the circuit (out and back)2 x 10 ft = 20 ft
Resistance of 6 AWG0.3951 ohm per 1000 ft; 0.0079 ohm for this circuit
Voltage drop0.237 V = 1.98% within 3%
Voltage at the load11.76 V
Power lost in the wire7.11 W
Ampacity of 6 AWG65 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 30 x 2 x 10 x 0.3951 / 1000 = 0.237 V, and 0.237 / 12 = 1.98%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.823.83131.928.1710*drop and current
161.312.4120.089.5913*drop and current
142.081.51512.6310.4820drop and current
123.310.9537.9411.0525drop and current
105.260.5994.9911.435too much drop
88.370.3773.1411.6250too much drop
613.30.2371.9811.7665smallest that passes
421.20.1491.2411.8585passes
326.70.1180.9911.88100passes
233.60.0940.7811.91115passes
142.40.0740.6211.93130passes
1/053.50.0590.4911.94150passes
2/067.40.0470.3911.95175passes
3/0850.0370.3111.96200passes
4/01070.0290.2511.97230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

30 A wire size by length

One-way length12V, 3%12V, 10%24V, 3%
5 ft (1.5 m)1010*10*
10 ft (3 m)610*10
15 ft (4.6 m)6108
20 ft (6.1 m)4106
25 ft (7.6 m)386
30 ft (9.1 m)386
40 ft (12.2 m)164
50 ft (15.2 m)1/063

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Worked example

30 A at 12 V, 10 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 10 = 20 ft of wire, and the allowed drop is 12 x 3 / 100 = 0.36 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 6 AWG (13.3 mm²), rated 65 A, the smallest size that passes both.

Same current at 24V

At 24 V the same 30 A may drop twice as many volts for the same 3%, so a 10 ft run needs 10 AWG instead of 6 AWG. The current rating does not change with voltage, so the ampacity floor stays the same. See the 24V chart.

Before you buy wire

Questions

What gauge wire for 30 amps at 12V over 20 feet?

4 at 3% drop and 10 at 10%, copper AWG.

How much voltage is lost carrying 30 amps through 10 feet of 6 AWG?

0.237 V, which is 1.98% of 12 V, and 7.1 W turned into heat in the wire. That uses 20 ft of wire, out and back.