Wire RunAll charts

DC wire size calculator

Enter the system voltage, the load in amps or watts and the one-way length from the battery or panel to the load. The calculator doubles the length for the return path, finds the smallest copper gauge that keeps the voltage drop within your limit and is rated for the current, and shows the drop, the voltage at the load and the power lost for any gauge. Use 3% for critical loads and 10% for non-critical lighting.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 8 AWG (8.37 mm²) copper or larger.

Voltage drop sets the size. 10 AWG would drop 3.33%, over your 3% limit. Ampacity alone would allow 14 AWG.

Check: 8 AWG (8.37 mm²)

Load current20 A
Wire in the circuit (out and back)2 x 10 ft = 20 ft
Resistance of 8 AWG0.6282 ohm per 1000 ft; 0.01256 ohm for this circuit
Voltage drop0.251 V = 2.09% within 3%
Voltage at the load11.75 V
Power lost in the wire5.03 W
Ampacity of 8 AWG50 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 20 x 2 x 10 x 0.6282 / 1000 = 0.251 V, and 0.251 / 12 = 2.09%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.822.55421.289.4510*drop and current
161.311.60613.3910.3913*drop and current
142.081.018.4210.9920too much drop
123.310.6355.2911.3625too much drop
105.260.43.3311.635too much drop
88.370.2512.0911.7550smallest that passes
613.30.1581.3211.8465passes
421.20.0990.8311.985passes
326.70.0790.6611.92100passes
233.60.0630.5211.94115passes
142.40.050.4111.95130passes
1/053.50.0390.3311.96150passes
2/067.40.0310.2611.97175passes
3/0850.0250.2111.98200passes
4/01070.020.1611.98230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

Worked example

20 A at 12 V, 10 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 10 = 20 ft of wire, and the allowed drop is 12 x 3 / 100 = 0.36 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 8 AWG (8.37 mm²), rated 50 A, the smallest size that passes both.

12V wire size chart at 3% drop

Amps5 ft
1.5 m
10 ft
3 m
15 ft
4.6 m
20 ft
6.1 m
25 ft
7.6 m
30 ft
9.1 m
40 ft
12.2 m
50 ft
15.2 m
5 A18141212101088
10 A14121088664
15 A1210866643
20 A128664432
30 A106643311/0
40 A8643211/02/0
50 A843211/02/03/0
60 A64311/01/03/04/0
80 A4*311/02/03/04/0over 4/0
100 A3*21/02/03/04/0over 4/0over 4/0
150 A1/0*1/02/04/0over 4/0over 4/0over 4/0over 4/0
200 A3/0*3/0*4/0over 4/0over 4/0over 4/0over 4/0over 4/0

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Charts for every voltage: 12V, 24V, 36V, 48V.

Wire gauge, resistance and rated amps

AWGmm²ohm per 1000 ftohm per kmRated ampsBasis
180.826.38520.948210chassis-wiring guidance
161.314.01613.175913chassis-wiring guidance
142.082.5258.284120NEC 310.16, 75 C
123.311.5885.2125NEC 310.16, 75 C
105.260.99893.277235NEC 310.16, 75 C
88.370.62822.06150NEC 310.16, 75 C
613.30.39511.296365NEC 310.16, 75 C
421.20.24850.815385NEC 310.16, 75 C
326.70.1970.6463100NEC 310.16, 75 C
233.60.15630.5128115NEC 310.16, 75 C
142.40.12390.4065130NEC 310.16, 75 C
1/053.50.098270.3224150NEC 310.16, 75 C
2/067.40.077930.2557175NEC 310.16, 75 C
3/0850.06180.2028200NEC 310.16, 75 C
4/01070.049010.1608230NEC 310.16, 75 C

Resistance: copper at 20 C. Rated amps for 14 AWG and larger: NEC (NFPA 70) Table 310.16, copper, 75 C column, which assumes 30 C ambient and no more than three current-carrying conductors together; hotter spaces and bundles lower it. 18 and 16 AWG are not in that table; their figures are common chassis-wiring guidance. NEC 240.4(D) also limits overcurrent protection on 14, 12 and 10 AWG to 15, 20 and 30 A.

Before you buy wire

Questions

Should I enter the one-way length or the total wire length?

The one-way length, from the source to the load. The calculator doubles it, because the current flows out on the positive and back on the negative. If your negative returns through a chassis or hull bond, the real circuit is different and you should measure it.

Why does the calculator sometimes pick a thicker wire than the voltage drop needs?

Every conductor has a current rating. On short runs a thin wire can keep the drop small and still be rated for less than the load draws, so the ampacity check decides the size.

What drop should I use?

A common rule is 3% for loads that suffer from low voltage, such as electronics, pumps, fridges, inverters and charging, and 10% for lighting and other non-critical loads. Marine tables built on ABYC E-11 use the same two figures.

Does it handle stranded wire?

The resistance figures are the standard values for copper at 20 C. Stranded cable of the same gauge has slightly higher resistance, and warm wire more again, so leave some margin when a result is close to the limit.