AWG to mm² conversion

AWG numbers fall as the wire gets thicker, and every three gauges roughly doubles the cross-section. Metric cable is sold by cross-section in mm². Where an AWG size falls between two metric sizes, use the next metric size up unless you have checked the drop and current for the smaller one.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 8 AWG (8.37 mm²) copper or larger.

Voltage drop sets the size. 10 AWG would drop 3.33%, over your 3% limit. Ampacity alone would allow 14 AWG.

Check: 8 AWG (8.37 mm²)

Load current20 A
Wire in the circuit (out and back)2 x 10 ft = 20 ft
Resistance of 8 AWG0.6282 ohm per 1000 ft; 0.01256 ohm for this circuit
Voltage drop0.251 V = 2.09% within 3%
Voltage at the load11.75 V
Power lost in the wire5.03 W
Ampacity of 8 AWG50 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 20 x 2 x 10 x 0.6282 / 1000 = 0.251 V, and 0.251 / 12 = 2.09%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.822.55421.289.4510*drop and current
161.311.60613.3910.3913*drop and current
142.081.018.4210.9920too much drop
123.310.6355.2911.3625too much drop
105.260.43.3311.635too much drop
88.370.2512.0911.7550smallest that passes
613.30.1581.3211.8465passes
421.20.0990.8311.985passes
326.70.0790.6611.92100passes
233.60.0630.5211.94115passes
142.40.050.4111.95130passes
1/053.50.0390.3311.96150passes
2/067.40.0310.2611.97175passes
3/0850.0250.2111.98200passes
4/01070.020.1611.98230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

AWG to mm² table

AWGmm²Solid diameter (mm)Nearest metric sizeNext metric size upohm per km
180.821.020.75 mm²1 mm²20.9482
161.311.291.5 mm²1.5 mm²13.1759
142.081.632.5 mm²2.5 mm²8.2841
123.312.054 mm²4 mm²5.21
105.262.596 mm²6 mm²3.2772
88.373.2610 mm²10 mm²2.061
613.34.1216 mm²16 mm²1.2963
421.25.1925 mm²25 mm²0.8153
326.75.8325 mm²35 mm²0.6463
233.66.5435 mm²35 mm²0.5128
142.47.3535 mm²50 mm²0.4065
1/053.58.2550 mm²70 mm²0.3224
2/067.49.2770 mm²70 mm²0.2557
3/08510.495 mm²95 mm²0.2028
4/010711.6895 mm²120 mm²0.1608

Diameter of a solid conductor from the AWG formula; stranded cable is larger overall. Metric sizes are the common IEC 60228 series.

Worked example

20 A at 12 V, 10 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 10 = 20 ft of wire, and the allowed drop is 12 x 3 / 100 = 0.36 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 8 AWG (8.37 mm²), rated 50 A, the smallest size that passes both.

24V quick chart at 3% drop

Amps5 ft
1.5 m
10 ft
3 m
20 ft
6.1 m
30 ft
9.1 m
50 ft
15.2 m
5 A1818141210
10 A181412108
20 A1412864
30 A10*10663
50 A8*8431
100 A3*3*21/03/0

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Before you buy wire

Questions

Is 6 mm² the same as 10 AWG?

Close. 10 AWG is 5.26 mm², so 6 mm² is slightly larger and carries the same current with a little less drop.