48V wire size chart

Find the current down the left and the one-way length across the top. Each cell is the smallest copper gauge that keeps the drop within the limit at 48 V and is rated for the current. For example, 30 A over 15 ft at 48 V needs 10 AWG at 3%. Change any number in the calculator for your own run.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 10 AWG (5.26 mm²) copper or larger.

Ampacity sets the size, not voltage drop. 12 AWG would keep the drop under 3%, but 30 A needs a conductor rated for at least that current: 10 AWG is rated 35 A (NEC 310.16, 75 C).

Check: 10 AWG (5.26 mm²)

Load current30 A
Wire in the circuit (out and back)2 x 15 ft = 30 ft
Resistance of 10 AWG0.9989 ohm per 1000 ft; 0.02997 ohm for this circuit
Voltage drop0.899 V = 1.87% within 3%
Voltage at the load47.1 V
Power lost in the wire27 W
Ampacity of 10 AWG35 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 30 x 2 x 15 x 0.9989 / 1000 = 0.899 V, and 0.899 / 48 = 1.87%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.825.74611.9742.2510*drop and current
161.313.6147.5344.3913*drop and current
142.082.2724.7345.7320drop and current
123.311.4292.9846.5725current too high
105.260.8991.8747.135smallest that passes
88.370.5651.1847.4350passes
613.30.3560.7447.6465passes
421.20.2240.4747.7885passes
326.70.1770.3747.82100passes
233.60.1410.2947.86115passes
142.40.1120.2347.89130passes
1/053.50.0880.1847.91150passes
2/067.40.070.1547.93175passes
3/0850.0560.1247.94200passes
4/01070.0440.0947.96230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

48V chart at 3% drop (critical loads)

Amps5 ft
1.5 m
10 ft
3 m
15 ft
4.6 m
20 ft
6.1 m
25 ft
7.6 m
30 ft
9.1 m
40 ft
12.2 m
50 ft
15.2 m
5 A1818181816161414
10 A1818161414121210
15 A14*14*14121212108
20 A14*141212101088
30 A10*10*10*108866
40 A8*8*8*88664
50 A8*8*886644
60 A6*6*6*66643
80 A4*4*4*4*4432
100 A3*3*3*3*3*321
150 A1/0*1/0*1/0*1/0*1/0*1/0*1/02/0
200 A3/0*3/0*3/0*3/0*3/0*3/0*3/0*3/0

48V chart at 10% drop (non-critical lighting)

Amps5 ft
1.5 m
10 ft
3 m
15 ft
4.6 m
20 ft
6.1 m
25 ft
7.6 m
30 ft
9.1 m
40 ft
12.2 m
50 ft
15.2 m
5 A1818181818181818
10 A1818181818181616
15 A14*14*14*14*14*14*1414
20 A14*14*14*14*14*141412
30 A10*10*10*10*10*10*10*10*
40 A8*8*8*8*8*8*8*8*
50 A8*8*8*8*8*8*8*8
60 A6*6*6*6*6*6*6*6*
80 A4*4*4*4*4*4*4*4*
100 A3*3*3*3*3*3*3*3*
150 A1/0*1/0*1/0*1/0*1/0*1/0*1/0*1/0*
200 A3/0*3/0*3/0*3/0*3/0*3/0*3/0*3/0*

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Worked example

30 A at 48 V, 15 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 15 = 30 ft of wire, and the allowed drop is 48 x 3 / 100 = 1.44 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 10 AWG (5.26 mm²), rated 35 A, the smallest size that passes both. Here the current rating, not the drop, decides it: 12 AWG would be enough for the drop alone.

Why 48V needs thinner wire than 12V

For the same power, current falls as voltage rises, and the allowed drop in volts rises with it. Both work in your favour: at 48 V a 1000 W load draws 20.8 A and may lose 1.44 V at 3%, against 83.3 A and 0.36 V at 12 V. Other charts: 12V, 24V, 36V.

Before you buy wire

Questions

What size wire for 20 amps at 48V over 20 feet?

12 AWG copper at 3% drop, or 14 AWG at 10%, from the chart above.