Wire RunAll charts

What size wire for 80 amps at 12V?

80 A over 10 ft one way at 12 V with a 3% drop limit needs 3 AWG copper. By current rating alone 4 AWG would do (85 A), so longer runs are decided by voltage drop and need thicker wire. The table gives every length from 5 to 50 ft.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 3 AWG (26.7 mm²) copper or larger.

Voltage drop sets the size. 4 AWG would drop 3.31%, over your 3% limit. Ampacity alone would allow 4 AWG.

Check: 3 AWG (26.7 mm²)

Load current80 A
Wire in the circuit (out and back)2 x 10 ft = 20 ft
Resistance of 3 AWG0.197 ohm per 1000 ft; 0.00394 ohm for this circuit
Voltage drop0.315 V = 2.63% within 3%
Voltage at the load11.68 V
Power lost in the wire25.2 W
Ampacity of 3 AWG100 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 80 x 2 x 10 x 0.197 / 1000 = 0.315 V, and 0.315 / 12 = 2.63%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.8210.21685.131.7810*drop and current
161.316.42653.555.5713*drop and current
142.084.0433.677.9620drop and current
123.312.54121.179.4625drop and current
105.261.59813.3210.435drop and current
88.371.0058.3810.9950drop and current
613.30.6325.2711.3765drop and current
421.20.3983.3111.685too much drop
326.70.3152.6311.68100smallest that passes
233.60.252.0811.75115passes
142.40.1981.6511.8130passes
1/053.50.1571.3111.84150passes
2/067.40.1251.0411.88175passes
3/0850.0990.8211.9200passes
4/01070.0780.6511.92230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

80 A wire size by length

One-way length12V, 3%12V, 10%24V, 3%
5 ft (1.5 m)4*4*4*
10 ft (3 m)34*4*
15 ft (4.6 m)14*4
20 ft (6.1 m)1/043
25 ft (7.6 m)2/042
30 ft (9.1 m)3/041
40 ft (12.2 m)4/021/0
50 ft (15.2 m)over 4/012/0

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Worked example

80 A at 12 V, 10 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 10 = 20 ft of wire, and the allowed drop is 12 x 3 / 100 = 0.36 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 3 AWG (26.7 mm²), rated 100 A, the smallest size that passes both.

Same current at 24V

At 24 V the same 80 A may drop twice as many volts for the same 3%, so a 10 ft run needs 4 AWG instead of 3 AWG. The current rating does not change with voltage, so the ampacity floor stays the same. See the 24V chart.

Before you buy wire

Questions

What gauge wire for 80 amps at 12V over 20 feet?

1/0 at 3% drop and 4 at 10%, copper AWG.

How much voltage is lost carrying 80 amps through 10 feet of 3 AWG?

0.315 V, which is 2.63% of 12 V, and 25.2 W turned into heat in the wire. That uses 20 ft of wire, out and back.

Related

Get the printable wire chart and new calculators by email

We are making a printable DC wire chart for the van, boat or workshop wall, and more calculators for 12V and solar work. Leave your email and we will send the chart when it is ready and tell you when a new calculator goes up. Free, nothing else.