What size wire for 10 amps at 12V?

10 A over 10 ft one way at 12 V with a 3% drop limit needs 12 AWG copper. By current rating alone 18 AWG would do (10 A, chassis-wiring guidance), so longer runs are decided by voltage drop and need thicker wire. The table gives every length from 5 to 50 ft.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 12 AWG (3.31 mm²) copper or larger.

Voltage drop sets the size. 14 AWG would drop 4.21%, over your 3% limit. Ampacity alone would allow 18 AWG.

Check: 12 AWG (3.31 mm²)

Load current10 A
Wire in the circuit (out and back)2 x 10 ft = 20 ft
Resistance of 12 AWG1.588 ohm per 1000 ft; 0.03176 ohm for this circuit
Voltage drop0.318 V = 2.65% within 3%
Voltage at the load11.68 V
Power lost in the wire3.18 W
Ampacity of 12 AWG25 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 10 x 2 x 10 x 1.588 / 1000 = 0.318 V, and 0.318 / 12 = 2.65%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.821.27710.6410.7210*too much drop
161.310.8036.6911.213*too much drop
142.080.5054.2111.4920too much drop
123.310.3182.6511.6825smallest that passes
105.260.21.6611.835passes
88.370.1261.0511.8750passes
613.30.0790.6611.9265passes
421.20.050.4111.9585passes
326.70.0390.3311.96100passes
233.60.0310.2611.97115passes
142.40.0250.2111.98130passes
1/053.50.020.1611.98150passes
2/067.40.0160.1311.98175passes
3/0850.0120.111.99200passes
4/01070.010.0811.99230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

10 A wire size by length

One-way length12V, 3%12V, 10%24V, 3%
5 ft (1.5 m)141818
10 ft (3 m)121614
15 ft (4.6 m)101412
20 ft (6.1 m)81412
25 ft (7.6 m)81210
30 ft (9.1 m)61210
40 ft (12.2 m)6108
50 ft (15.2 m)4108

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Worked example

10 A at 12 V, 10 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 10 = 20 ft of wire, and the allowed drop is 12 x 3 / 100 = 0.36 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 12 AWG (3.31 mm²), rated 25 A, the smallest size that passes both.

Same current at 24V

At 24 V the same 10 A may drop twice as many volts for the same 3%, so a 10 ft run needs 14 AWG instead of 12 AWG. The current rating does not change with voltage, so the ampacity floor stays the same. See the 24V chart.

Before you buy wire

Questions

What gauge wire for 10 amps at 12V over 20 feet?

8 at 3% drop and 14 at 10%, copper AWG.

How much voltage is lost carrying 10 amps through 10 feet of 12 AWG?

0.318 V, which is 2.65% of 12 V, and 3.2 W turned into heat in the wire. That uses 20 ft of wire, out and back.