3000W inverter wire size at 24V

A 3000 W inverter running flat out on 24 V draws about 147.1 A from the battery at 85% efficiency, or 138.9 A at 90%: I = P / (V x efficiency) = 3000 / (24 x 0.85) = 147.1 A, rounded up. Over 5 ft one way at 3% drop that needs 1/0 AWG copper. Size the cable for the inverter's continuous rating, and check the cable and fuse sizes its manual gives.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 1/0 AWG (53.5 mm²) copper or larger.

Ampacity sets the size, not voltage drop. 6 AWG would keep the drop under 3%, but 147.1 A needs a conductor rated for at least that current: 1/0 AWG is rated 150 A (NEC 310.16, 75 C).

Check: 1/0 AWG (53.5 mm²)

Load current147.1 A
Wire in the circuit (out and back)2 x 5 ft = 10 ft
Resistance of 1/0 AWG0.09827 ohm per 1000 ft; 0.00098 ohm for this circuit
Voltage drop0.145 V = 0.6% within 3%
Voltage at the load23.86 V
Power lost in the wire21.3 W
Ampacity of 1/0 AWG150 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 147.1 x 2 x 5 x 0.09827 / 1000 = 0.145 V, and 0.145 / 24 = 0.6%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.829.39239.1314.6110*drop and current
161.315.90824.6118.0913*drop and current
142.083.71415.4820.2920drop and current
123.312.3369.7321.6625drop and current
105.261.4696.1222.5335drop and current
88.370.9243.8523.0850drop and current
613.30.5812.4223.4265current too high
421.20.3661.5223.6385current too high
326.70.291.2123.71100current too high
233.60.230.9623.77115current too high
142.40.1820.7623.82130current too high
1/053.50.1450.623.86150smallest that passes
2/067.40.1150.4823.89175passes
3/0850.0910.3823.91200passes
4/01070.0720.323.93230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

3000W inverter cable size by length at 24V

One-way length85%: 147.1 A, 3%90%: 138.9 A, 3%85%: 147.1 A, 10%
3 ft (0.9 m)1/0*1/0*1/0*
5 ft (1.5 m)1/0*1/0*1/0*
6 ft (1.8 m)1/0*1/0*1/0*
8 ft (2.4 m)1/0*1/0*1/0*
10 ft (3 m)1/0*1/0*1/0*
12 ft (3.7 m)1/0*1/0*1/0*
15 ft (4.6 m)1/0*1/0*1/0*

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Worked example

147.1 A at 24 V, 5 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 5 = 10 ft of wire, and the allowed drop is 24 x 3 / 100 = 0.72 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 1/0 AWG (53.5 mm²), rated 150 A, the smallest size that passes both. Here the current rating, not the drop, decides it: 6 AWG would be enough for the drop alone.

When the battery sags

Current rises as battery voltage falls. The same 3000 W at 22 V and 85% draws 160.5 A, so if you run the inverter hard on a low battery, check that current against the cable's rating too. A fuse or breaker on the positive cable, close to the battery, protects the cable itself.

Before you buy wire

Questions

How many amps does a 3000W inverter draw at 24V?

About 147.1 A at full load and 85% efficiency (3000 / (24 x 0.85)), or 138.9 A at 90%. At light load it draws far less.

What size cable for a 3000W inverter at 24V over 10 feet?

1/0 AWG copper at 3% drop, sized for 147.1 A.