3000W inverter wire size at 12V

A 3000 W inverter running flat out on 12 V draws about 294.2 A from the battery at 85% efficiency, or 277.8 A at 90%: I = P / (V x efficiency) = 3000 / (12 x 0.85) = 294.2 A, rounded up. Over 5 ft one way at 3% drop that needs more than a single 4/0 copper. Size the cable for the inverter's continuous rating, and check the cable and fuse sizes its manual gives.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

No single copper conductor up to 4/0 AWG passes.

294.2 A is more than the 230 A rating of 4/0. Split the load into parallel runs, or use a higher system voltage to cut the current.

Check: 4/0 AWG (107 mm²)

Load current294.2 A
Wire in the circuit (out and back)2 x 5 ft = 10 ft
Resistance of 4/0 AWG0.04901 ohm per 1000 ft; 0.00049 ohm for this circuit
Voltage drop0.144 V = 1.2% within 3%
Voltage at the load11.86 V
Power lost in the wire42.4 W
Ampacity of 4/0 AWG230 A (NEC 310.16, 75 C) too small

Vd = I x 2L x R / 1000 = 294.2 x 2 x 5 x 0.04901 / 1000 = 0.144 V, and 0.144 / 12 = 1.2%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.8218.785156.54-6.7810*drop and current
161.3111.81598.460.1813*drop and current
142.087.42961.94.5720drop and current
123.314.67238.937.3325drop and current
105.262.93924.499.0635drop and current
88.371.84815.410.1550drop and current
613.31.1629.6910.8465drop and current
421.20.7316.0911.2785drop and current
326.70.584.8311.42100drop and current
233.60.463.8311.54115drop and current
142.40.3653.0411.64130drop and current
1/053.50.2892.4111.71150current too high
2/067.40.2291.9111.77175current too high
3/0850.1821.5211.82200current too high
4/01070.1441.211.86230current too high

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

3000W inverter cable size by length at 12V

One-way length85%: 294.2 A, 3%90%: 277.8 A, 3%85%: 294.2 A, 10%
3 ft (0.9 m)over 4/0over 4/0over 4/0
5 ft (1.5 m)over 4/0over 4/0over 4/0
6 ft (1.8 m)over 4/0over 4/0over 4/0
8 ft (2.4 m)over 4/0over 4/0over 4/0
10 ft (3 m)over 4/0over 4/0over 4/0
12 ft (3.7 m)over 4/0over 4/0over 4/0
15 ft (4.6 m)over 4/0over 4/0over 4/0

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Worked example

294.2 A at 12 V, 5 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 5 = 10 ft of wire, and the allowed drop is 12 x 3 / 100 = 0.36 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

No single copper conductor up to 4/0 passes. 294.2 A is above the 230 A that 4/0 is rated for. Common answers are conductors in parallel (the NEC allows paralleling in 1/0 and larger, with matching length, material and terminations) or a higher system voltage, which cuts the current.

Why no single cable is listed for 3000W at 12V

294.2 A is more than the 230 A that NEC Table 310.16 gives 4/0 copper in the 75 C column, so no single conductor in this calculator is rated for it. The usual answers are a higher battery voltage (the 3000W inverter at 24V draws 147.1 A) or two conductors in parallel per pole; the NEC allows paralleling in 1/0 and larger, with matching length, material and terminations. Battery and welding cable with a higher temperature rating, sized to ABYC E-11 or the cable maker's own table, is allowed more current than the NEC 75 C column, so some installers use a single larger cable here. This calculator stays with the conservative NEC figures.

Before you buy wire

Questions

How many amps does a 3000W inverter draw at 12V?

About 294.2 A at full load and 85% efficiency (3000 / (12 x 0.85)), or 277.8 A at 90%. At light load it draws far less.

What size cable for a 3000W inverter at 12V over 10 feet?

No single copper conductor up to 4/0 passes at 3% drop, sized for 294.2 A.