Wire RunAll charts

1000W inverter wire size at 12V

A 1000 W inverter running flat out on 12 V draws about 98.1 A from the battery at 85% efficiency, or 92.6 A at 90%: I = P / (V x efficiency) = 1000 / (12 x 0.85) = 98.1 A, rounded up. Over 5 ft one way at 3% drop that needs 3 AWG copper. Size the cable for the inverter's continuous rating, and check the cable and fuse sizes its manual gives.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 3 AWG (26.7 mm²) copper or larger.

Ampacity sets the size, not voltage drop. 4 AWG would keep the drop under 3%, but 98.1 A needs a conductor rated for at least that current: 3 AWG is rated 100 A (NEC 310.16, 75 C).

Check: 3 AWG (26.7 mm²)

Load current98.1 A
Wire in the circuit (out and back)2 x 5 ft = 10 ft
Resistance of 3 AWG0.197 ohm per 1000 ft; 0.00197 ohm for this circuit
Voltage drop0.193 V = 1.61% within 3%
Voltage at the load11.81 V
Power lost in the wire19 W
Ampacity of 3 AWG100 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 98.1 x 2 x 5 x 0.197 / 1000 = 0.193 V, and 0.193 / 12 = 1.61%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.826.26452.25.7410*drop and current
161.313.9432.838.0613*drop and current
142.082.47720.649.5220drop and current
123.311.55812.9810.4425drop and current
105.260.988.1711.0235drop and current
88.370.6165.1411.3850drop and current
613.30.3883.2311.6165drop and current
421.20.2442.0311.7685current too high
326.70.1931.6111.81100smallest that passes
233.60.1531.2811.85115passes
142.40.1221.0111.88130passes
1/053.50.0960.811.9150passes
2/067.40.0760.6411.92175passes
3/0850.0610.5111.94200passes
4/01070.0480.411.95230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

1000W inverter cable size by length at 12V

One-way length85%: 98.1 A, 3%90%: 92.6 A, 3%85%: 98.1 A, 10%
3 ft (0.9 m)3*3*3*
5 ft (1.5 m)3*3*3*
6 ft (1.8 m)3*3*3*
8 ft (2.4 m)333*
10 ft (3 m)223*
12 ft (3.7 m)123*
15 ft (4.6 m)1/013*

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Worked example

98.1 A at 12 V, 5 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 5 = 10 ft of wire, and the allowed drop is 12 x 3 / 100 = 0.36 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 3 AWG (26.7 mm²), rated 100 A, the smallest size that passes both. Here the current rating, not the drop, decides it: 4 AWG would be enough for the drop alone.

When the battery sags

Current rises as battery voltage falls. The same 1000 W at 11 V and 85% draws 107 A, so if you run the inverter hard on a low battery, check that current against the cable's rating too. A fuse or breaker on the positive cable, close to the battery, protects the cable itself.

Before you buy wire

Questions

How many amps does a 1000W inverter draw at 12V?

About 98.1 A at full load and 85% efficiency (1000 / (12 x 0.85)), or 92.6 A at 90%. At light load it draws far less.

What size cable for a 1000W inverter at 12V over 10 feet?

2 AWG copper at 3% drop, sized for 98.1 A.