2000W inverter wire size at 12V

A 2000 W inverter running flat out on 12 V draws about 196.1 A from the battery at 85% efficiency, or 185.2 A at 90%: I = P / (V x efficiency) = 2000 / (12 x 0.85) = 196.1 A, rounded up. Over 5 ft one way at 3% drop that needs 3/0 AWG copper. Size the cable for the inverter's continuous rating, and check the cable and fuse sizes its manual gives.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 3/0 AWG (85 mm²) copper or larger.

Ampacity sets the size, not voltage drop. 2 AWG would keep the drop under 3%, but 196.1 A needs a conductor rated for at least that current: 3/0 AWG is rated 200 A (NEC 310.16, 75 C).

Check: 3/0 AWG (85 mm²)

Load current196.1 A
Wire in the circuit (out and back)2 x 5 ft = 10 ft
Resistance of 3/0 AWG0.0618 ohm per 1000 ft; 0.00062 ohm for this circuit
Voltage drop0.121 V = 1.01% within 3%
Voltage at the load11.88 V
Power lost in the wire23.8 W
Ampacity of 3/0 AWG200 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 196.1 x 2 x 5 x 0.0618 / 1000 = 0.121 V, and 0.121 / 12 = 1.01%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.8212.521104.34-0.5210*drop and current
161.317.87565.634.1213*drop and current
142.084.95241.267.0520drop and current
123.313.11425.958.8925drop and current
105.261.95916.3210.0435drop and current
88.371.23210.2710.7750drop and current
613.30.7756.4611.2365drop and current
421.20.4874.0611.5185drop and current
326.70.3863.2211.61100drop and current
233.60.3072.5511.69115current too high
142.40.2432.0211.76130current too high
1/053.50.1931.6111.81150current too high
2/067.40.1531.2711.85175current too high
3/0850.1211.0111.88200smallest that passes
4/01070.0960.811.9230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

2000W inverter cable size by length at 12V

One-way length85%: 196.1 A, 3%90%: 185.2 A, 3%85%: 196.1 A, 10%
3 ft (0.9 m)3/0*3/0*3/0*
5 ft (1.5 m)3/0*3/0*3/0*
6 ft (1.8 m)3/0*3/0*3/0*
8 ft (2.4 m)3/0*3/0*3/0*
10 ft (3 m)3/0*3/0*3/0*
12 ft (3.7 m)3/03/0*3/0*
15 ft (4.6 m)4/03/03/0*

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Worked example

196.1 A at 12 V, 5 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 5 = 10 ft of wire, and the allowed drop is 12 x 3 / 100 = 0.36 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 3/0 AWG (85 mm²), rated 200 A, the smallest size that passes both. Here the current rating, not the drop, decides it: 2 AWG would be enough for the drop alone.

When the battery sags

Current rises as battery voltage falls. The same 2000 W at 11 V and 85% draws 214 A, so if you run the inverter hard on a low battery, check that current against the cable's rating too. A fuse or breaker on the positive cable, close to the battery, protects the cable itself.

Before you buy wire

Questions

How many amps does a 2000W inverter draw at 12V?

About 196.1 A at full load and 85% efficiency (2000 / (12 x 0.85)), or 185.2 A at 90%. At light load it draws far less.

What size cable for a 2000W inverter at 12V over 10 feet?

3/0 AWG copper at 3% drop, sized for 196.1 A.