DC-DC charger wire size

A DC-DC charger moves current from the starter battery and alternator to a house battery. The input cable usually carries a little more current than the charger's rated output, because of conversion losses, so check the input current in its manual and size for that. Charging is a critical load: use 3%.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 4 AWG (21.2 mm²) copper or larger.

Voltage drop sets the size. 6 AWG would drop 3.95%, over your 3% limit. Ampacity alone would allow 8 AWG.

Check: 4 AWG (21.2 mm²)

Load current40 A
Wire in the circuit (out and back)2 x 15 ft = 30 ft
Resistance of 4 AWG0.2485 ohm per 1000 ft; 0.00745 ohm for this circuit
Voltage drop0.298 V = 2.48% within 3%
Voltage at the load11.7 V
Power lost in the wire11.9 W
Ampacity of 4 AWG85 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 40 x 2 x 15 x 0.2485 / 1000 = 0.298 V, and 0.298 / 12 = 2.48%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.827.66263.854.3410*drop and current
161.314.81940.167.1813*drop and current
142.083.0325.258.9720drop and current
123.311.90615.8810.0925drop and current
105.261.1999.9910.835drop and current
88.370.7546.2811.2550too much drop
613.30.4743.9511.5365too much drop
421.20.2982.4811.785smallest that passes
326.70.2361.9711.76100passes
233.60.1881.5611.81115passes
142.40.1491.2411.85130passes
1/053.50.1180.9811.88150passes
2/067.40.0940.7811.91175passes
3/0850.0740.6211.93200passes
4/01070.0590.4911.94230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

DC-DC charger cable size by length at 12V, 3% drop

One-way length20 A30 A40 A50 A60 A
5 ft (1.5 m)1210886
10 ft (3 m)86644
15 ft (4.6 m)66433
20 ft (6.1 m)64321
25 ft (7.6 m)43211/0
30 ft (9.1 m)4311/01/0

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Worked example

40 A at 12 V, 15 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 15 = 30 ft of wire, and the allowed drop is 12 x 3 / 100 = 0.36 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 4 AWG (21.2 mm²), rated 85 A, the smallest size that passes both.

Fusing both ends

A charger run connects two batteries, and either one can feed a short in the cable. A fuse near each battery protects the cable from both sides. Use the fuse sizes the charger's manual gives.

Before you buy wire

Questions

Should I size for the input or the output side?

Each side separately. The input side runs from the starter battery and carries the input current; the output side runs to the house battery. The two runs often differ in length.

Related

Get the printable wire chart and new calculators by email

We are making a printable DC wire chart for the van, boat or workshop wall, and more calculators for 12V and solar work. Leave your email and we will send the chart when it is ready and tell you when a new calculator goes up. Free, nothing else.