Solar panel to charge controller wire size

Use the string's operating voltage (Vmp) and current (Imp) for voltage drop. Panels wired in series raise the voltage and keep the current, which is why longer roof runs often use a series string. The ampacity check uses a different current: NEC 690.8 takes 1.25 x the short-circuit current (Isc) as the maximum, and asks for conductors rated for 1.25 x that, so 1.56 x Isc in total.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 12 AWG (3.31 mm²) copper or larger.

Voltage drop sets the size. 14 AWG would drop 4.21%, over your 3% limit. Ampacity alone would allow 18 AWG.

Check: 12 AWG (3.31 mm²)

Load current10 A
Wire in the circuit (out and back)2 x 30 ft = 60 ft
Resistance of 12 AWG1.588 ohm per 1000 ft; 0.09528 ohm for this circuit
Voltage drop0.953 V = 2.65% within 3%
Voltage at the load35.05 V
Power lost in the wire9.53 W
Ampacity of 12 AWG25 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 10 x 2 x 30 x 1.588 / 1000 = 0.953 V, and 0.953 / 36 = 2.65%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.823.83110.6432.1710*too much drop
161.312.416.6933.5913*too much drop
142.081.5154.2134.4820too much drop
123.310.9532.6535.0525smallest that passes
105.260.5991.6635.435passes
88.370.3771.0535.6250passes
613.30.2370.6635.7665passes
421.20.1490.4135.8585passes
326.70.1180.3335.88100passes
233.60.0940.2635.91115passes
142.40.0740.2135.93130passes
1/053.50.0590.1635.94150passes
2/067.40.0470.1335.95175passes
3/0850.0370.135.96200passes
4/01070.0290.0835.97230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

Wire size for 10 A from the panels, by length and string voltage

One-way length18 V Vmp, 3%36 V Vmp, 3%72 V Vmp, 3%
10 ft (3 m)141618
20 ft (6.1 m)101416
30 ft (9.1 m)81214
40 ft (12.2 m)81014
50 ft (15.2 m)61012
75 ft (22.9 m)4810
100 ft (30.5 m)4610

Voltage drop only, at 10 A Imp. Then check ampacity: for a panel with Isc 11 A, 1.56 x 11 = 17.2 A, which needs at least 14 AWG (20 A) before any derating for heat on a roof. Use whichever of the two is thicker. One-way length; the math uses twice that.

Worked example

10 A at 36 V, 30 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 30 = 60 ft of wire, and the allowed drop is 36 x 3 / 100 = 1.08 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 12 AWG (3.31 mm²), rated 25 A, the smallest size that passes both.

Wire for the location

Conductors on a roof or in sunlight need insulation rated for it (PV wire or USE-2 in the NEC), and roof heat lowers the current a conductor may carry. The calculator's ampacity figures assume 30 C ambient.

Before you buy wire

Questions

Which voltage do I enter for a solar string?

The string voltage at maximum power, Vmp, which is the sum of the panel Vmp figures for panels in series. Use the string current, Imp, as the load.

Why does a 3% drop matter on the panel side?

Every volt lost in the wire is power the panels make but the controller never sees. At 3% you lose about 3% of the string power as heat in the wire.

Related

Get the printable wire chart and new calculators by email

We are making a printable DC wire chart for the van, boat or workshop wall, and more calculators for 12V and solar work. Leave your email and we will send the chart when it is ready and tell you when a new calculator goes up. Free, nothing else.