Wire RunAll charts

Trolling motor wire size

Use the motor's maximum current draw from its manual and the one-way distance from the battery to the motor's plug. A bow-mount motor with the batteries at the stern can need a long run. The table uses 50 A; change the calculator to your motor's figure.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 4 AWG (21.2 mm²) copper or larger.

Voltage drop sets the size. 6 AWG would drop 3.29%, over your 3% limit. Ampacity alone would allow 8 AWG.

Check: 4 AWG (21.2 mm²)

Load current50 A
Wire in the circuit (out and back)2 x 20 ft = 40 ft
Resistance of 4 AWG0.2485 ohm per 1000 ft; 0.00994 ohm for this circuit
Voltage drop0.497 V = 2.07% within 3%
Voltage at the load23.5 V
Power lost in the wire24.8 W
Ampacity of 4 AWG85 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 50 x 2 x 20 x 0.2485 / 1000 = 0.497 V, and 0.497 / 24 = 2.07%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.8212.7753.2111.2310*drop and current
161.318.03233.4715.9713*drop and current
142.085.0521.0418.9520drop and current
123.313.17613.2320.8225drop and current
105.261.9988.322235drop and current
88.371.2565.2422.7450too much drop
613.30.793.2923.2165too much drop
421.20.4972.0723.585smallest that passes
326.70.3941.6423.61100passes
233.60.3131.323.69115passes
142.40.2481.0323.75130passes
1/053.50.1970.8223.8150passes
2/067.40.1560.6523.84175passes
3/0850.1240.5123.88200passes
4/01070.0980.4123.9230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

Wire size for a 50 A trolling motor, by length and voltage

One-way length12V, 50 A, 3%24V, 50 A, 3%36V, 50 A, 3%
10 ft (3 m)488*
15 ft (4.6 m)368
20 ft (6.1 m)246
25 ft (7.6 m)146
30 ft (9.1 m)1/034

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Worked example

50 A at 24 V, 20 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 20 = 40 ft of wire, and the allowed drop is 24 x 3 / 100 = 0.72 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 4 AWG (21.2 mm²), rated 85 A, the smallest size that passes both.

Marine wiring

On a boat, ABYC E-11 is the usual standard for DC wiring. It asks for stranded copper, rated for the location, and an overcurrent device near the battery. Motor makers often list a cable size and breaker by length; if theirs is thicker than this result, use theirs.

Before you buy wire

Questions

Why does a 36V trolling motor use thinner wire than a 12V one?

Higher voltage motors draw less current for the same thrust, and the allowed drop in volts is larger. Both mean thinner wire for the same run.