Bilge pump wire size

A bilge pump that sees low voltage pumps less water, so treat it as a critical load and use 3%. Take the current from the pump's label or manual and measure the run from the battery or panel to the pump.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 10 AWG (5.26 mm²) copper or larger.

Voltage drop sets the size. 12 AWG would drop 4.23%, over your 3% limit. Ampacity alone would allow 18 AWG.

Check: 10 AWG (5.26 mm²)

Load current8 A
Wire in the circuit (out and back)2 x 20 ft = 40 ft
Resistance of 10 AWG0.9989 ohm per 1000 ft; 0.03996 ohm for this circuit
Voltage drop0.32 V = 2.66% within 3%
Voltage at the load11.68 V
Power lost in the wire2.56 W
Ampacity of 10 AWG35 A (NEC 310.16, 75 C) ok

Vd = I x 2L x R / 1000 = 8 x 2 x 20 x 0.9989 / 1000 = 0.32 V, and 0.32 / 12 = 2.66%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.822.04317.039.9610*too much drop
161.311.28510.7110.7113*too much drop
142.080.8086.7311.1920too much drop
123.310.5084.2311.4925too much drop
105.260.322.6611.6835smallest that passes
88.370.2011.6811.850passes
613.30.1261.0511.8765passes
421.20.080.6611.9285passes
326.70.0630.5311.94100passes
233.60.050.4211.95115passes
142.40.040.3311.96130passes
1/053.50.0310.2611.97150passes
2/067.40.0250.2111.98175passes
3/0850.020.1611.98200passes
4/01070.0160.1311.98230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

Bilge pump wire size by length at 12V, 3% drop

One-way length3 A5 A8 A10 A15 A
5 ft (1.5 m)1818161412
10 ft (3 m)1614121210
15 ft (4.6 m)141210108
20 ft (6.1 m)14121086
25 ft (7.6 m)1210886
30 ft (9.1 m)1210866

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Worked example

8 A at 12 V, 20 ft one way, 3% drop allowed. The current goes out and comes back, so the circuit is 2 x 20 = 40 ft of wire, and the allowed drop is 12 x 3 / 100 = 0.36 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 10 AWG (5.26 mm²), rated 35 A, the smallest size that passes both.

Before you buy wire

Questions

Can bilge pump wire run through the bilge?

Only wire rated for wet locations, with connections kept as high as you can. Marine standards such as ABYC E-11 set the rules for that; follow them.