12V LED light wire size

Lighting is the usual example of a non-critical load, so the calculator is set to 10% here. Add up the watts of every light on the circuit; the calculator converts watts to amps at your voltage. If the lights dim or flicker at 10%, or the driver needs a steady voltage, use 3%.

Watts are converted: amps = watts / volts.
Source to load. The circuit is 2 x this length (out and back).

Use 18 AWG (0.82 mm²) copper or larger.

Voltage drop and ampacity both land on this size. The 18 AWG current figure is chassis-wiring guidance, not an NEC rating.

Check: 18 AWG (0.82 mm²)

Load current36 W / 12 V = 3 A
Wire in the circuit (out and back)2 x 20 ft = 40 ft
Resistance of 18 AWG6.385 ohm per 1000 ft; 0.2554 ohm for this circuit
Voltage drop0.766 V = 6.38% within 10%
Voltage at the load11.23 V
Power lost in the wire2.3 W
Ampacity of 18 AWG10 A (chassis-wiring guidance) ok

Vd = I x 2L x R / 1000 = 3 x 2 x 20 x 6.385 / 1000 = 0.766 V, and 0.766 / 12 = 6.38%. Length L in feet, R in ohms per 1000 ft.

AWGmm²Drop (V)Drop (%)At load (V)Rated (A)Result
180.820.7666.3811.2310*smallest that passes
161.310.4824.0211.5213*passes
142.080.3032.5311.720passes
123.310.1911.5911.8125passes
105.260.12111.8835passes
88.370.0750.6311.9250passes
613.30.0470.411.9565passes
421.20.030.2511.9785passes
326.70.0240.211.98100passes
233.60.0190.1611.98115passes
142.40.0150.1211.99130passes
1/053.50.0120.111.99150passes
2/067.40.0090.0811.99175passes
3/0850.0070.0611.99200passes
4/01070.0060.0511.99230passes

* chassis-wiring guidance; 14 AWG and up: NEC Table 310.16, copper, 75 C column.

Runs in your browser; nothing you type is sent anywhere. Copper conductors only.

LED lighting wire size by length at 12V

One-way length1 A, 10%3 A, 10%5 A, 10%8 A, 10%5 A, 3%
5 ft (1.5 m)1818181818
10 ft (3 m)1818181814
15 ft (4.6 m)1818181612
20 ft (6.1 m)1818161412
25 ft (7.6 m)1818161410
30 ft (9.1 m)1818141210

Copper, minimum AWG. * ampacity, not voltage drop, sets this size. "over 4/0" means no single copper conductor up to 4/0 passes: shorten the run, use a higher system voltage or run conductors in parallel. Length is one way; the math uses twice that, out and back.

Worked example

36 W (3 A) at 12 V, 20 ft one way, 10% drop allowed. The current goes out and comes back, so the circuit is 2 x 20 = 40 ft of wire, and the allowed drop is 12 x 10 / 100 = 1.2 V. Voltage drop is Vd = I x 2L x R / 1000, with R in ohms per 1000 ft:

Answer: 18 AWG (0.82 mm²), rated 10 A as chassis-wiring guidance, the smallest size that passes both.

Before you buy wire

Questions

Can I use very thin wire for LED strips?

Short runs at low current often pass on drop with 18 AWG, but check the current rating too, and the fuse protecting the circuit must suit the wire.